LCL filters are extensively utilized in Grid-connected inverters due to their exceptional capability in suppressing high-frequency harmonics. The active damping method is commonly employed to mitigate the resonance peak of the LCL filter. However, this control strategy induces a shift in the natural resonance point. To address this issue, a novel active damping control strategy based on the principle of equivalent transformation is proposed in this paper, which not only effectively suppresses the resonance peak but also avoids deviation from the natural resonance point. Finally, experiments are carried out on a three-phase LCL Grid-connected inverter, and the experimental results show that the control strategy has good steady-state performance, dynamic response, and robustness under both rigid and ultra-weak network conditions.