Operation performance of an ultralow-temperature cascade refrigeration freezer with environmentally friendly refrigerants R290-R170.

Environ Sci Pollut Res Int

Department of Building Environment and Energy Engineering, School of Mechanics and Civil Engineering, China University of Mining and Technology, Xuzhou, 221116, China.

Published: March 2023

In the present study, the operation performance of an ultralow-temperature cascade refrigeration freezer is experimentally researched. The natural refrigerants R290-R170 are adopted as high-temperature and low-temperature fluids. The experimental test is conducted in a type laboratory with a dry bulb temperature of 32.0 °C and a wet bulb temperature of 26.5 °C. Different state monitors are set to display the system operation performance, and several temperature monitors are arranged to study the pull-down performance and temperature variations in the freezer. Based on the established experimental rig, three freezing temperatures, including - 40 °C, - 80 °C, and - 86 °C, are measured and compared. The results show that it takes about 240 min for the freezer to be pulled down to - 80 °C. During the pull-down period, different monitors all experience rapid temperature drop, and the power consumption reduces from 1461.4 W to 997.5 W. Once the target temperature is achieved, the freezer comes into periodic start-stop operation. With the set temperature ranging from - 40 °C to - 86 °C, the inlet temperature of two compressors gradually decreases, while the discharge temperature has an increase trend. The cooling effect of the pre-cooled condenser reduces with the freezing temperature, while the long connection pipe has opposite variation profile. Moreover, it is observed that for different freezing temperatures, most of the space in the freezer can be cooled down to the target temperature. It is confirmed that the present ultralow-temperature freezer can be used for the storage and transportation of COVID-19 vaccines. However, it is also found that the cascade refrigeration system is not suitable for high freezing temperature, due to high power consumption and extensive start-stop switch of refrigeration system.

Download full-text PDF

Source
http://www.ncbi.nlm.nih.gov/pmc/articles/PMC9686239PMC
http://dx.doi.org/10.1007/s11356-022-24310-zDOI Listing

Publication Analysis

Top Keywords

operation performance
12
cascade refrigeration
12
temperature
12
performance ultralow-temperature
8
ultralow-temperature cascade
8
refrigeration freezer
8
refrigerants r290-r170
8
bulb temperature
8
performance temperature
8
freezing temperatures
8

Similar Publications

Want AI Summaries of new PubMed Abstracts delivered to your In-box?

Enter search terms and have AI summaries delivered each week - change queries or unsubscribe any time!