Objectives: In a job site, a portable fan is often used to ventilate a confined space. When a portable fan is applied to such a space, the actual ventilation flow rate must be accurately estimated in advance because the safety level of contaminant and oxygen concentrations in the space will determine the ventilation requirements. When a portable fan is used with a flexible duct, the actual flow rate of the fan decreases due to the friction and duct bending loss of the duct. Intending to show the decline of a fan performance, the author conducted laboratory experiments and reported the quantitative effect of the friction and duct bending loss of a flexible duct to the flow rate of a portable fan.

Methods: Four commercial portable fans of different specifications were procured for the experiments, and the decline of the performance of each portable fan due to the friction loss etc. of a connected flexible duct was investigated by measuring actual flow rate.

Results: The flow rate showed an obvious decrease from the rated flow rate when a flexible duct was connected. Connection of a straight polyester flexible duct and a straight aluminum flexible duct reduced the flow rates to 81.2 - 52.9% and less than 50%, respectively. The flow rate decreased with an increase of the bend angle of the flexible duct.

Conclusion: It is recommended that flow rate check of a portable fan should be diligently carried out in every job site.

Download full-text PDF

Source
http://www.ncbi.nlm.nih.gov/pmc/articles/PMC5478525PMC
http://dx.doi.org/10.1539/joh.16-0091-OPDOI Listing

Publication Analysis

Top Keywords

flexible duct
28
flow rate
28
portable fan
20
friction duct
12
duct bending
12
bending loss
12
duct
11
flow
9
decline performance
8
portable
8

Similar Publications

Want AI Summaries of new PubMed Abstracts delivered to your In-box?

Enter search terms and have AI summaries delivered each week - change queries or unsubscribe any time!