This study was designed to examine the in vitro bactericidal activity of hydrogen peroxide against Legionella. We tested hydrogen peroxide (Peroxy Ag⁺) at 600 ppm to evaluate Legionella survival in a simulated dental treatment water system equipped with Water Hygienization Equipment (W.H.E.) device that was artificially contaminated. When Legionella pneumophila serogroup (sg) 1 was exposed to Peroxy Ag⁺ for 60 min we obtained a two decimal log reduction. High antimicrobial efficacy was obtained with extended periods of exposure: four decimal log reduction at 75 min and five decimal log reduction at 15 h of exposure. Involving a simulation device (Peroxy Ag⁺ is flushed into the simulation dental unit waterlines (DUWL)) we obtained an average reduction of 85% of Legionella load. The product is effective in reducing the number of Legionella cells after 75 min of contact time (99.997%) in the simulator device under test conditions. The Peroxy Ag⁺ treatment is safe for continuous use in the dental water supply system (i.e., it is safe for patient contact), so it could be used as a preventive option, and it may be useful in long-term treatments, alone or coupled with a daily or periodic shock treatment.
Download full-text PDF |
Source |
---|---|
http://www.ncbi.nlm.nih.gov/pmc/articles/PMC4962286 | PMC |
http://dx.doi.org/10.3390/ijerph13070745 | DOI Listing |
Enter search terms and have AI summaries delivered each week - change queries or unsubscribe any time!