High-energy switches and trigger generators are required for MJ-level capacitor banks. We have developed a compact gas switch and a matched series injection trigger generator. A series inductance is required for isolation of the trigger pulse from the surrounded circuit. A saturable inductor is employed here because low inductance is needed after the switch breakdown. The switch is of coaxial two-electrode design with electrodynamic acceleration of a spark channel. The switch operates at atmospheric pressure. The spark gap can be triggered reliably down to zero voltage (at 50 kV self-breakdown voltage) with less than 35 ns timing jitter. Energy losses in this spark gap have been accurately investigated. The main results are as follows: energy losses in the switch do not exceed 4% at voltages higher than 15 kV, i.e., when operation voltage exceeds ∼36% of the self-breakdown voltage. The spark gap is designed for 24 kV charging voltage, at a current up to 250 kA, and ∼70 C charge transfer. In this paper, we present a design for the spark gap, inductor and trigger generator. Test bed schematics and results of the tests are also described.

Download full-text PDF

Source
http://dx.doi.org/10.1063/1.4937359DOI Listing

Publication Analysis

Top Keywords

spark gap
16
gas switch
8
trigger generator
8
self-breakdown voltage
8
energy losses
8
switch
6
spark
5
voltage
5
two-electrode gas
4
switch electrodynamical
4

Similar Publications

Want AI Summaries of new PubMed Abstracts delivered to your In-box?

Enter search terms and have AI summaries delivered each week - change queries or unsubscribe any time!