Characterization of sulfate reducing bacteria isolated from cooling towers.

Environ Monit Assess

Department of Biology, Faculty of Science, Istanbul University, Istanbul, Turkey.

Published: May 2005

In this study, the occurrence and metabolic capacities of sulfate reducing bacteria (SRB) were studied in 36 water samples taken from cooling towers of 30 different buildings, such as hotels and business centres in Istanbul. SRB were present in 14 cooling towers out of 30 (46.6%) buildings and while the lowest concentration of SRB was 10 cells/mL, the highest concentration was determined as 10(4) cells/mL. After the distribution of SRB within cooling towers was determined, several strains of SRB were isolated and characterized metabolically. The isolated strains were composed of vibroid cells, growing anaerobically by using sulfate as electron acceptor and lactate or pyruvate as electron donor. They could be related to the genus Desulfovibrio. In addition, the recorded temperature of water samples was between 12 and 33 degrees C and a significant relationship between the number of SRB and the water temperatures was not found.

Download full-text PDF

Source
http://dx.doi.org/10.1007/s10661-005-1612-xDOI Listing

Publication Analysis

Top Keywords

cooling towers
16
sulfate reducing
8
reducing bacteria
8
water samples
8
srb cooling
8
srb
6
characterization sulfate
4
bacteria isolated
4
cooling
4
isolated cooling
4

Similar Publications

Water footprint which is not the water footprint: Critical review of the article by Müller et al. (2024).

J Environ Manage

January 2025

Výzkumný ústav Vodohospodářský T. G. Masaryka, Podbabská 2582/30, 160 00 Praha, Czech Republic. Electronic address:

This paper presents a critical analysis of the article "Comparison of cooling tower blowdown and enhanced make up water treatment to minimize cooling water footprint" by Müller et al. (2024), which claims to reduce the water footprint (WF) of cooling circuits. The WF concept, introduced in 2002, has evolved with two main approaches: the "volumetric" approach, quantifying water consumption, and the "impact-oriented" approach, assessing impacts associated with water usage.

View Article and Find Full Text PDF

Direct air capture (DAC) is a promising technology for mitigating global climate change but suffers from low efficiency, small scale, and high cost due to the dilute atmospheric CO, limited size of air contactors, and heat-driven CO release. Here, we propose combining DAC with widely used industrial cooling towers to extract CO from the air and using electrolysis to release the captured CO at room temperature. We first prepare a buffered absorbent solution consisting of sodium glycinate, glycine, and sodium chloride for effective CO capture from the air, solving the incompatibility problem of the cooling towers with conventional absorbents.

View Article and Find Full Text PDF

Performance assessment of solar tower collector based integrated system for the cogeneration of power and cooling.

Heliyon

November 2024

Department of Electrical Engineering, College of Engineering, Majmaah University, Al-Majmaah, 11952, Saudi Arabia.

Integrating solar energy systems is an essential measure in advancing worldwide sustainability objectives and offers a sustainable, environmentally friendly approach to reducing greenhouse gas emissions and pollutants. To this direction, the proposed system integrating solar tower collector, supercritical CO, organic Rankine cycle, and single effect absorption refrigeration cycles shows potential as an efficient and sustainable solution for meeting energy and cooling demands. A detailed thermodynamic evaluation has been performed to gain valuable understanding of the energy and exergy performance, enabling the assessment of thermal and exergy efficiencies, exergy destructions, and heat losses.

View Article and Find Full Text PDF

In this paper, a wind tunnel experiment was carried out to study the atmospheric flow and pollutant diffusion around a super-large natural ventilation cooling tower of a nuclear power plant. Considering the effect of the natural ventilation of the cooling tower, with the chimney as the center, X-type hot-wire probes were used to measure the average flow field and turbulence structure of the atmosphere around the cooling tower and other complexes, and pollutant diffusion studies were carried out by tracer experiments. The results show that the super-large natural ventilation cooling tower and its thermal plume emission have a significant effect on pollutant flow and diffusion, changing the trajectory of the plume.

View Article and Find Full Text PDF

Increase in energy demand is shaping both developed and developing countries globally. As a result, the endeavour to reduce carbon emissions also encompasses electrical energy storage systems to ensure environmentally friendly power production and distribution. Currently, the scientific community is actively exploring and developing new storage technologies for this purpose.

View Article and Find Full Text PDF

Want AI Summaries of new PubMed Abstracts delivered to your In-box?

Enter search terms and have AI summaries delivered each week - change queries or unsubscribe any time!