The aim of the study was to compare radon concentrations in neighbouring hospital buildings which were constructed in different years during the period 1963-2000 and are located in areas with similar radon potential. The value of arithmetic mean (AM) radon concentration in soil gas amounted to 14,464 Bq m(-3). In a hospital built 40 years ago, the AM radon concentration in the cellar was 38.4+/-36.7 Bq m(-3) and on higher levels it was 17.1+/-10.3 Bq m(-3). In a hospital built 16 years ago, these values equaled 45.5+/-47.2 Bq m(-3) and 20.4+/-12.5 Bq m(-3), respectively. In the newest hospital, built three years ago, radon concentration (AM) in a cellar was 32.3+/-27.4 Bq m(-3) and the respective value on higher levels amounted to 20.4+/-12.6 Bq m(-3). When comparing radon concentrations in the cellars, no statistically significant differences were found. Similarly, no statistically significant differences were observed between radon concentrations measured on higher levels in investigated hospital buildings.