A cascade control system comprising the primary and secondary controllers suffers from a cascade-type integral windup problem in which the output saturation of the secondary control loop can considerably increase the integral part of the primary control loop. In this paper, we present a new predictive antiwindup technique that can completely eliminate the possibility of secondary controller output saturation, resulting in no cascade-type integral windup phenomenon. The proposed method does not require any type of process models; thus, its implementation is simple and straightforward, which is a very favorable advantage compared to the model-based antiwindup techniques from the practical viewpoint.