Four reduced-height (5 m) BS 8414-1 façade flammability tests were conducted, three having mineral-filled aluminium composite material (ACM-A2) with polyisocyanurate (PIR) and phenolic (PF) foam and stone wool (SW) insulation, the fourth having polyethylene-filled ACM (ACM-PE) with PIR insulation. Each façade was constructed from a commercial façade engineer's design, and built by practising façade installers. The ACM-PE/PIR façade burnt so ferociously it was extinguished after 13.
View Article and Find Full Text PDFThe toxic smoke production of four rainscreen façade systems were compared during large-scale fire performance testing on a reduced height BS 8414 test wall. Systems comprising 'non-combustible' aluminium composite material (ACM) with polyisocyanurate (PIR), phenolic foam (PF) and stone wool (SW) insulation, and polyethylene-filled ACM with PIR insulation were tested. Smoke toxicity was measured by sampling gases at two points - the exhaust duct of the main test room and an additional 'kitchen vent', which connects the rainscreen cavity to an occupied area.
View Article and Find Full Text PDF