Publications by authors named "Albert Treytl"

We investigated non-invasive flow rate measurements in heating, ventilation, and air conditioning (HVAC) systems utilizing thermal transduction instead of commonly used ultrasonic techniques. The proposed thermal flow transduction comprises two temperature sensors and a heater, all mounted non-invasively on the outer surface of metal-pipes and, therefore, not disturbing the fluid flow inside. One temperature sensor measures the heater temperature, whereas the other one, mounted upstream of the heater, follows the fluid temperature for reference.

View Article and Find Full Text PDF

We present a thermal flow sensor designed for measuring air as well as water flow velocities in heating, ventilation, and air conditioning (HVAC) systems. The sensor is designed to integrate the flow along the entire diameter of the pipe also quantifying the volume flow rate of the streaming fluid where the calorimetric principle in constant temperature operation is utilized as a readout method. In the constant temperature mode, a controller keeps a specific excess temperature between sensing elements at a constant level resulting in a flow dependent heater voltage.

View Article and Find Full Text PDF